Transformer IQ

Transformer IQ

TransformerIQ provides real-time, continuous intelligence for Vault, Padmount or Poletop distribution transformers.

  • Prevent overload
  • Identify imbalance
  • Accurately determine end-of-line voltage
  • Optimize volt/VAR initiatives
  • Smooth the introduction of renewables onto the grid
Product Information
Order & Spec Info
Downloads
  • Capabilities

    • Power Quality Monitoring
    • Voltage Sag and Swell
    • Voltage and Current Harmonics through the 31st harmonic on A, B & C Phases
    • True Power Factor
    • Fault Monitoring
    • Fault Phase Indication
    • Fault Magnitude
    • Fault Duration
    • Temperature Monitoring
    • Winding Temperature & Loss of Life Prediction
    • Top Oil, Bottom Oil, LTC Oil or Multi-tank Temperatures
    • Enclosure & Ambient Temperatures
    • Network Vault Transformer Monitoring
    • Affordably monitor multiple transformers in rooms or cabinets
    • Discrete data for each individual transformer

    Features

    • Package designed for retrofit
    • All operational and fault information captured with feeder sensing
    • Calculated hot spot temperatures on all monitored windings
    • Provisions for Smart Grid mesh radios

    Benefits

    • Substation-type transformer monitoring, for small power transformers
    • Extremely cost effective
    • Improve outage management
    • Improve fault isolation time with line fault information
    • Set alarms for temperature, overload, voltage sag/swell
  • Ordering Information

    Transformer IQ Monitor for Residential for Distribution Applications
    TIQ-P4-W = Options, see below
    W = Wireless Communication OptionsG1
    G2
    G3
    G4
    G5
    G6
    G7
    = No Wireless Communication
    = Ingenu Radio
    = 3GQuad Band Cellular
    = CDMA Quad Band Cellular
    = Wi-Fi Connection
    = Landis+Gyr Radio
    = Silver Springs Network
    Transformer IQ Monitor Distribution Processor & Separate Termination Enclosure for Vault Applications
    TIQ-VAULT-V-W-X-Y = Options, see below
    V = Voltage Input Options(blank)
    VLT1
    = None
    = 3-Phase Voltage Input Module
    W = Wireless Communication OptionsG1
    G2
    G3
    G4
    G5
    G6
    G7
    G8
    = No Wireless Communication
    = Ingenu Radio
    = 3GQuad Band Cellular
    = CDMA Quad Band Cellular
    = Wi-Fi Connection
    = Landis+Gyr Radio
    =Ethernet
    =RS-485 Analog
    X = Input / Output Option(blank)
    D
    R
    = None
    = 8 Discrete Inputs
    = 8 Relay Outputs
    Y = Bus Bar Clamp Option(blank)
    B
    = None
    = Bus Bar Clamps

    Specifications

    GENERAL
    Communications:MODBUS, DNP3; Ethernet, WiFi, GSM, ASCII over RS232,
    ASCII over RS485
    Integrated Socket-mounted Remote Communications:Ingenu; Silver Spring Networks;
    Landis+Gyr; WiFi, GSM/EDGE, or CDMA modem
    Operating Environment:-40 C to 85 °C for fully submersible encapsulated version
    CHANNELS/MODEL
    P4Vault
    RMS Voltage:312
    RMS Current:3 Neutral12 Neutrals
    Fault Current:312
    Fault Duration:312
    Discrete Inputs:524
    Analog Inputs:N/A2
    Temperatures:46
    Internal Case Temperature:11
    Cooling Load:03
    LTC Change Duration:01
    LTC Change Energy:01
  • Brochures