CELLGUARD™ Wired

cellguard-base-coordinator-unit-hero.psd

CELLGUARD™ Wired

The CELLGUARD™ wired Battery Monitoring System (BMS) delivers economical, yet highly accurate and reliable remote health analysis of stationary batteries in applications with high electromagnetic noise. Battery operators are provided with continuous 24/7 monitoring of key battery performance indicators to help enable proactive maintenance, ensure battery performance, and deliver uninterrupted power when it matters the most.

ENSURE UPTIME WITH 24/7 MONITORING

Utility personnel are provided with continuous 24/7 monitoring of key battery performance indicators to help enable proactive maintenance, ensure battery performance, and deliver uninterrupted uptime when it matters the most.

KEY ADVANTAGES

Wired-Icon-Battery-Health.psd

STATE OF HEALTH

The BMS helps analyze data trends related to battery state of health, simplifying the detection of potential issues for operators to optimize battery usage.

LTC Icon Regulate.psd

INTERNAL RESISTANCE TESTING AND PERFORMANCE TRENDING

The BMS tests a given battery’s internal resistance at a pre-determined interval. The results are then collected and presented as a trend providing the user with genuine DC power plant performance insight.

DTM - Icon - Power Factor.psd

DISCHARGE EVENTS

Battery discharge events are recorded automatically (including battery voltage, string voltage, discharge current and discharge capacity).

Wired-Icon-Parameter.psd

PARAMETER AND ALARM THRESHOLDS

The user can set / modify many measurement parameters and thresholds either locally or remotely. The system invokes a permission hierarchy to manage administrative access.

CELLGUARD Wired - Install - Wide.psd
SOLID HARDWARE

The CELLGUARD™ Wired Battery Monitoring System ideal for all mission-critical DC power plants including UPS, data center, rail / subway, airport, telco, utility power generation, utility substation, and manufacturing, as well as fire and safety systems.

Wired - Hardware - Sensors.psd

BATTERY SENSORS

One battery sensor per battery is capable of monitoring internal resistance, voltage, and temperature, delivering a comprehensive battery state of health analysis.

UNITE-Wired-Hardware.psd

BASE COORDINATOR UNIT

The base coordinator unit (BCU) records critical performance elements including alarms and discharge events. Alarm parameters and thresholds are managed through the BCU which also delivers real-time system data through the web-based UNITE™ Battery Asset Management Software.

The BCU can communicate via RS485, Ethernet, MODBUS/RTU, MODBUS/TCP, and SNMP protocols.  Data derived from the BMS is easily integrated into most third-party systems. 

Wired - Hardware - String.psd

STRING SENSOR & CURRENT TRANSDUCER

One string sensor per string, in conjunction with a string current transducer provides monitoring of the string voltage, current, and ambient temperature.

UNITE Grid Overview Wide-Wired.psd
SOFTWARE FEATURES

 

UNITE™ allows you to seamlessly and remotely drill down through your network of battery plants, strings, and individual batteries. Gain access to valuable performance insight data, enable cost-saving condition-based maintenance planning, and simplify your compliance reporting.

UNITE Grid Battery - Report.psd

SIMPLIFY REPORTING

With a single click, a battery string report PDF can be generated to streamline reporting and compliance requirements. Reports include the latest battery data, a string overview table and graph, battery reference information, battery threshold details, and more.

UNITE Grid Battery - Map.psd

PLANT MAP VIEW

Visualize your entire plant network geographically in a single map view. Visually confirm the status of all plants and quickly key in on those that may require attention or maintenance.


UNITE Grid Battery - Battery.psd

BATTERY VIEW

Dive into the present and historical performance data of individual batteries within a string. Visualize key battery performance indicators and trending data to pinpoint batteries in need of replacement with accuracy.

UNITE Grid Battery - Discharge.psd

DISCHARGE VIEW

UNITE™ provides a graphical timeline view of every string discharge event for advanced performance analysis and NERC compliance reporting. Discharge data includes start time, end time, voltage, temperature, and current.


 

ONCE THE PRODUCT SHIPS, WE'RE JUST GETTING STARTED

 

The Franklin Electric Grid Solution Technical and Field Support Teams are here to assist with training, installation, and support. Our Field team will come to your site for training or installation supervision and our Support Center staff is available to assist with troubleshooting, warranty processing, and software installation support.

System Components

cellguard-base-systemcomponents-01.png

1. Control Module

2. Battery Sensor Module

3. String Sensor Module

4. Current Transducer

6. CELLTRAQ Data Management Software

Specifications

Environmental Measurements

  • Operating temperature: -10°C to 50°C
  • Humidity: 5% to 95%

 

Monitoring Capability

  • Maximum batteries on a single String: 180
  • Control module string maximum: 6
  • Control module battery maximum: 360

Include 1 Relay and 2 Dry Contact Inputs

Specifications

  • Battery types: 2V, 6V, 12V (capacity less than 3000AH)
  • Insulation: 2000 VAC
  • Weight (Coordinator): 0.3 Kg
  • Weight (Battery Sensor): 75 g
  • Weight (String Sensor): 80 g

Controller Module Communication Interfaces

  • Serial Comm. Port: RS485 Modbus/RTU
  • RJ45 Ethernet Comm. Port: SNMP, Modbus/TCP
  • RJ22 Module Comm. Port: COM1-COM3 UART

 

Power Requirements

  • Base coordinator unit: 14-36 VDC 40W, external power supplies available
  • Battery sensor: < 13mA (1.2V, 2V) or 7mA (6V, 12V) from battery
  • String sensor: 10.8 to 13.8VDC, 2W, power from control module

 

Approvals & Certifications

  • EMC Certification: CISPR 11, IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-11
  • Compliance: CE & FCC

 

Reliability

  • Auto reboot trigger: Build-in WDT
  • MTBF: 100,000 hours

 

Measurement & Accuracy

Component Range Accuracy
String Voltage 20 to 800V +/- 0.5%
Battery voltage 2V, 6V, 12V +/- 0.1%
Battery resistance 50 to 65535uΏ +/- 2%, 1uΏ
Battery temperature -5°C to 99.9°C +/- 1°C
String current 0 to 1000A +/- 2%
Ambient temperature -5°C to 99.9°C +/- 1°C

 

 

 

 

 

 

Dimensions

cellguard-base-specs-01.png

1. Alarm indicator lights

2. Power input

3. String sensor power

4. Dry contact relays 

5. AUX inputs

6. USB-B, USB-A and Ethernet

7. Communication ports

BATTERY SENSOR

cellguard-batterysensor-specs-01.png

Battery Sensor Components

1. Indicator light

2. Battery connection port

3. Communication ports

STRING SENSOR

cellguard-stringsensor-specs-01.png

String Sensor Components

1. Indicator light

2. Battery sensor connection port

3. Communication ports

4. Power input

Model Description
CGBC-350-HWD CELLGUARD™ wired battery monitoring base coordinator unit,
utilizes CONVERGE™ interface manages 6 strings maximum, 300
cells on one string maximum, 360 cells on a module maximum.

POWER SUPPLY

Model Description
CGBC-DC-72-WD Power supply for 18-72 VDC. Includes input and output wiring.
CGBC-DC-370-WD Power supply for 120-370 VDC. Includes input and output wiring.
CGBC-DC-1500-WD Power supply for 200-1500 VDC. Includes input and output wiring.
CGBC-AC-1224-WD Power Supply for 85-264 VAC. Includes Type – A wall outlet
(NEMA1-15) for North America.

BATTERY SENSOR

Model Description
CGS3-02V-WD CELLGUARD™ wired battery monitoring battery sensor module for 2V batteries
CGS3-06V-WD CELLGUARD™ wired battery monitoring battery sensor module for 6V batteries
CGS3-12V-WD CELLGUARD™ wired battery monitoring battery sensor module for 12V batteries.

STRING SENSOR KIT

Model Description
CGTC3-600-WD CELLGUARD™ wired battery monitoring string sensor module with ambient temperature sensor, 1000A maximum, includes current transducer

Included in the Kit

  • Temperature/Current (TC) Module
  • Current Transducer
  • Interconnect Return Cable, 8 meter, with RJ22 plugs
  • Spare RJ22 plugs (qty 18)
  • Interconnect Cable, 30 cm, with RJ22 plugs
  • Current Transducer Cable with Temperature Sensor

SENSOR ADDRESSING MODULE

Model Description
CGS3-AMM-WD Sensor module address modifier

BATTERY HARNESSES

Model Description
CGS3-25BH-WD CELLGUARD™ wired battery harness, 25 cm
CGS3-50BH-WD CELLGUARD™ wired battery harness, 50 cm
CGS3-80BH-WD CELLGUARD™ wired battery harness, 80 cm

BATTERY INTERCONNECT CABLES

Model Description
CGS3-30CBL-WD CELLGUARD™ wired battery interconnect cable, 30 cm, with RJ22 plugs
CGS3-70CBL-WD CELLGUARD™ wired battery interconnect cable, 70 cm, with RJ22 plugs
CGS3-100CBL-WD CELLGUARD™ wired battery interconnect cable, 100 cm, with RJ22 plugs
CGS3-800CBL-WD CELLGUARD™ wired battery interconnect cable, 8 m, with RJ22 plugs
CGS3-RJ22-WD CELLGUARD™ spare RJ22 plugs (qty 100)

BATTERY TABS (8 Packs)

8 packs of battery tabs are included with CELLGUARD™ Wired Battery Monitoring systems at no cost, however, quantities must be specified upon ordering.

Model Description
429-0000015 CELLGUARD™ wired battery tab, 8 mm, U-type (qty 8)
429-0000016 CELLGUARD™ wired battery tab, 6.5 mm, Ring (qty 8)
429-0000017 CELLGUARD™ wired battery tab, 8 mm, Ring (qty 8)
429-0000018 CELLGUARD™ wired battery tab, 10 mm, U-type (qty 8) Model

BATTERY TABS (50 Packs)

Model Description
CGS3-BT6-WD CELLGUARD™ wired battery tab, 6.5 mm, Ring (qty 50)
CGS3-BT8-WD CELLGUARD™ wired battery tab, 8 mm, Ring (qty 50)
CGS3-BT10-WD CELLGUARD™ wired battery tab, 10 mm, U-type (qty 50)