CGBC-300-WD : CELLGUARD™ wired battery monitoring control module, 120 volts AC.
CGBC-300-WD-48V : CELLGUARD™ wired battery monitoring control module, 48 volts DC.
CGS3-01V-WD : CELLGUARD™ wired battery monitoring battery sensor module for Ni-Cad.
CGS3-02V-WD : CELLGUARD™ wired battery monitoring battery sensor module for 2V batteries.
CGS3-06V-WD : CELLGUARD™ wired battery monitoring battery sensor module for 6V batteries.
CGS3-12V-WD : CELLGUARD™ wired battery monitoring battery sensor module for 12V batteries.
CGVTC3-600-WD : CELLGUARD™ wired battery monitoring string sensor module with ambient
temperature sensor, 1000A maximum, includes current transducer.
CGS3-AMM-WD : Sensor module address modifier
Environmental
Operating temperature: -5°C to 50°C
Humidity: 5% to 95%
Monitoring Capability
Maximum batteries on a single String: 300
Control module string maximum: 6
Control module battery maximum: 360
Power Requirements
Control module: 85 to 264VAC, DC48V or 110V to 370VDC, 10W
Battery sensor module: < 13mA (1.2V, 2V) or 7mA (6V, 12V) from battery
String sensor module: 8 to 13VDC, 1 W, power from control module
Controller Module Communication Interfaces
RS485
Ethernet Port (10/100M)
Meets MODBUS/RTU, MODBUS/TCP, and SNMP protocol
Specifications
Battery Types
1.2V, 2V, 6V, 12V (capacity less than 3000AH)
Insulation
2000 VAC
Weight
Control module: 0.3 Kg
Battery sensor module: 75 g
String sensor module: 80 g
Approvals & Certifications
EMC: EN61326-1:2013 EN61326-2-1:2013
Safety: EN61010-1:2010, UL61010-1:2013
Reliability
Auto reboot trigger: built-in WDT
MTBF: 100,000 hours