The CELLTRON™ Secure Power Battery Tester provides a simple method to screen the state-of-health of popularly sized 6 volt and 12 volt sealed lead-acid batteries for security systems, emergency lighting, mobility vehicles, and uninterruptible power supplies.

SMALL BATTERY EVALUATION

The CELLTRON™ Secure Power Batery Tester provides a simple method to screen the state-of-health of 6 volt and 12 volt sealed lead-acid batteries.

Secure Power - Tester Fire - Wide.psd
KEY ADVANTAGES

Genstart - Icon - Conductance.psd

ACCURATE CONDUCTANCE TESTING

Utilizes enhanced conductance technology, a method recognized by IEEE standards, for the testing of lead-acid batteries with proven correlation to battery capacity.

Genstart - Icon - 6-12 V.psd

6/12 Volt Battery Testing

Provides off-line testing of 6 and 12 volt nominal batteries from 1.2 to approximately 55 ampere hours in capacity.

Genstart - Icon - Compliance.psd

NFPA-72 COMPLIANCE

An easy and economical means to execute routine testing that meets NFPA-72 standards requiring routine cell/unit voltage and Ohmic testing for batteries in fire alarm systems.

Secure Power - Tester Screen - Wide.psd
SECURE YOUR SAFETY SYSTEMS

Rest assured with routine battery testing of the batteries powering your common safety systems.

FAST TESTING

Battery voltage and conductance are displayed in less than 10 seconds.

SAFETY SYSTEMS

Perfect for testing batteries used in security systems, fire alarms, emergency lighting, mobility vehicles, and small UPS systems.

ENSURE POWER

Ensure the operation of critical systems despite power loss.

Applications

  • Sealed lead-acid batteries for security systems, emergency lighting, mobility vehicles, uninterruptible power supplies, and more

 

Power Requirements

  • Powered by the battery under test

 

Display

  • 4 Position LED alpha-numeric readout
  • LED mode indication

Interface Operations

  • Patent pending clips designed for a wide range of applications

 

Housing Material

  • Acid resistant ABS plastic

 

Calibration

  • Franklin Electric will work with each customer to establish a regular calibration program if it is required by their quality or other management system
Voltage Range 6.0 to 14.0 VDC
Conductance Range 20 - 1200 Mhos/Siemens
Battery Capacity Range 1.2 Ah to 55 Ah
Operating Temperature 0 to 120 degree F) -18 to 50 degree C
Storage Temperature -4 to 180°F (-20 to 82°C)
Dimensions 7.5" X 3.5" X 2.0"
(230 mm X 102 mm X 65 mm)
Weight 1 lb (427 g)

Secure Power

Model Description
SCP-100 CELLTRON Secure Power Battery Tester and clips